Oxygen-Service Cleaning of Cryogenic Tanks: Steps, Inspection and Acceptance Criteria

KRİYOJENİK DEPOLAMA TANKLARI
KRİYOJENİK DEPOLAMA TANKLARI

Looking for a cryogenic storage tank?

Cryoteknik manufactures cryogenic storage tanks for LIN, LOX, LAR, LNG, CO2 and N2O.

Cryogenic storage tanksRequest a quote →

Oxygen is not flammable, but it supports and accelerates combustion. An oil film, metal chips or cleaning-agent residue that is harmless in air can become an ignition source in oxygen. That is why LOX tanks, valves and piping go through “cleaning for oxygen service” before commissioning. This article summarises the steps and acceptance criteria based on ISO 23208 and CGA G-4.1 (Asian edition AIGA 012/19).

Which equipment needs oxygen cleaning?

According to AIGA 012/19, the cleaning requirement applies to surfaces in contact with gas or liquid containing more than 23.5 % oxygen by volume. The direct reference for cryogenic vessels is ISO 23208 (Cryogenic vessels — Cleanliness for cryogenic service). Its first edition (2005) was based on EN 12300. The current edition is ISO 23208:2017 with Amendment 1 of 2020. In Europe it is published as EN ISO 23208:2019 and has replaced EN 12300. The standard specifies minimum cleanliness requirements for all surfaces in contact with the cryogenic fluid. The aim is both to reduce the risk of equipment malfunction and to ensure safety against ignition in contact with oxygen or oxidizing fluids.

Typical contaminants

  • Oils, greases and thread lubricants
  • Cleaning-agent residues
  • Metal particles, chips and burrs
  • Fibres and dust

For welded fabrication ISO 23208 is clear: foreign matter such as chips, oxide scale and weld spatter is not acceptable. The 2017 edition also requires the root pass of pipe welds to be protected (e.g. with forming gas) to prevent gross porosity. Cleaning is therefore planned together with the welding procedure and the assembly sequence, not at the end of fabrication. Parts that will be inaccessible after assembly are cleaned and inspected before assembly.

Cleaning steps

ISO 23208 does not prescribe a specific cleaning method. Any procedure that meets the requirements of clause 4 may be used, on two conditions: the solvent or cleaning agent must be compatible with all materials being cleaned, particularly plastics, and any agents that are not oxygen-compatible must be completely removed from equipment cleaned for oxygen service. The steps below summarise typical practice according to CGA G-4.1 / AIGA 012/19.

  1. Planning and risk assessment: The type and location of contamination are identified and the cleaning agent is selected accordingly. Dead ends and liquid traps are identified in advance.
  2. Pre-cleaning: Gross contamination is removed mechanically, by blasting, wire brushing or grinding. The resulting debris is removed by vacuuming or by blowing out with dry, oil-free air or nitrogen.
  3. Main cleaning: An aqueous (alkaline, acid, detergent, hot water/steam), solvent or semi-aqueous (emulsion) method is used, applied by immersion, circulation, spraying or wiping. Solvents must be of stabilised grade. Almost all solvents and their residues are flammable in oxygen, so they must be removed completely.
  4. Rinsing: Done immediately after cleaning, before the surface dries. For alkaline and acid methods, rinsing continues until the outlet water pH is within ±0.2 of the inlet water pH.
  5. Drying: Purging with dry, oil-free air or nitrogen, with heating if required. The surface is considered dry when the outlet gas dew point is –30 °C or lower. If solvent was used, purging continues until no solvent is detected in the outlet gas.

The standard also defines “dry, oil-free gas”: dew point –40 °C or lower, oil content 5.0 mg/m³ or less. Standard workshop compressed air does not meet this automatically.

Where pickling and passivation of stainless steel surfaces is required, ASTM A380 / A967 are used as references.

Inspection methods

MethodWhat is doneApprox. detection limit for oil on stainless steel
White lightVisual inspection without magnification; particles above 50 µm are visible500–1700 mg/m²
UV (black) lightApplied to surfaces that pass white light; shows fluorescent contaminants40–1500 mg/m²
Wipe testSurface wiped with a clean lint-free cloth; cloth examined under white and UV light30–600 mg/m²
Water break testWater film must remain unbroken for at least 5 seconds30–60 mg/m²
Solvent extractionNon-volatile residue measured by weighing or light transmission<10 mg/m²

The detection limits in the table are taken from AIGA 012/19, Table 4. ISO 23208 Annex A (informative) states the following:

  • Direct inspection with white light or daylight is the most common method. It can detect the hydrocarbon level of 500 mg/m² in clause 4.2. Its effectiveness depends on surface roughness.
  • UV light is applied at a wavelength of about 370 nm, from 10–20 cm, in darkness. Because some vegetable oils do not fluoresce, it is not sufficient on its own for oxygen service and should be supported by white light and/or wipe tests.
  • The wipe test is used when the white light result is inconclusive. It is not recommended for rough or cast surfaces and can only be a spot check on large surfaces.
  • The solvent method is for inaccessible surfaces and larger installations. The amount of residue is determined by mass, by volume or by light transmission.

The standard also requires the chosen inspection method to be documented, the results to be recorded, and the method itself not to cause contamination. If inspection reveals contamination, the part is partially or totally recleaned. Repeated rejection calls for a re-evaluation of the cleaning method.

Acceptance criteria

ISO 23208 (cryogenic vessels):

  • Foreign matter such as chips, oxide scale and weld spatter is not acceptable.
  • Particles visible under daylight or white light without magnification are not acceptable. More stringent particle requirements may apply depending on system design.
  • Free water shall not be detectable by visual examination.
  • For oxygen and oxidizing fluids, hydrocarbons, paint, adhesives, sealants and protective coatings shall not be visible under white light unless they are oxygen-compatible according to ISO 21010.
  • The maximum hydrocarbon contamination (oil, grease etc.) is 500 mg/m². According to the 2020 amendment this value is guidance; a lower value may be requested depending on the application.

CGA G-4.1 / AIGA 012/19 §9.1 (stricter):

  • Non-volatile residue less than 220 mg/m²
  • Particles between 500 and 1000 µm: no more than 22 per m²; no particles larger than 1000 µm
  • Total particles no more than 110 mg/m² or 825 per m²
  • Isolated fibres no longer than 2000 µm, no accumulation

In practice the customer specification determines which criterion applies. Gas companies often require their own, stricter limits. The acceptance criterion should be agreed in writing at the order stage.

Post-cleaning protection and identification

  • Cleaned items are protected so that they stay clean until use. Purging and sealing are applied to prevent moisture condensation during storage.
  • Packaging and plugs in contact with clean surfaces must be clean and removable without leaving residue. Packaging must withstand handling and storage conditions and be sealable and waterproof.
  • Any protective gas must be dry, oil-free and dust-free. Pressurising gas is kept at low pressure; under ISO 23208:2017 a warning tag is required if the pressure exceeds 0.5 bar.
  • No adhesives are used on surfaces that will contact oxygen. Duct tape is not oxygen-compatible.
  • Cleaned parts are stored separately from uncleaned parts.
  • Evidence of conformity: A certificate accompanies the equipment, or a label is fixed to the packaging or equipment. For oxygen service the marking is “ISO 23208 – cleaned oxygen”; for other cryogenic fluids it is “ISO 23208”. If a protective gas is used, its type and pressure are legibly indicated.

Conclusion

Oxygen-service cleaning is not a “final wipe”. If the choice of cleaning agent, rinsing, drying-gas quality, quantitative inspection and post-cleaning protection are not managed together, a tank that leaves the shop clean can be recontaminated on site. A documented cleaning procedure and recorded inspection results are the most basic safety evidence for a tank in LOX service.

Sources

  • ISO 23208:2005 and ISO 23208:2017 / Amd 1:2020, Cryogenic vessels — Cleanliness for cryogenic service (EN ISO 23208:2019)
  • AIGA 012/19 (derived from CGA G-4.1), Cleaning of Equipment for Oxygen Service